ELECTRICAL DATA (Sizes 2 through 4)
Optidrive VTC Size 2
| Model No.
|
| ODE/ODEF-xxxxx-IN |
|
22150 |
22220 |
24150 |
24220 |
24400 |
|
1.5 |
2.2 |
1.5 |
2.2 |
4.0 |
|
| Model No.
|
| ODE/ODEF-xxxxx-USA |
|
22020 |
22030 |
24020 |
24030 |
24050 |
|
2.0 |
3.0 |
2.0 |
3.0 |
5.0 |
|
Supply
voltage/
phases |
V +/- 10% |
|
220-240/ 1Ø |
380-480/ 3Ø |
Supply fuse or
MCB rating |
A |
|
20 |
30 |
10 |
10 |
20 |
|
0-240/ 3Ø |
0-480/ 3Ø |
| Output Amps |
A |
| (overloaded 110%) |
|
|
7 |
10.5 |
4.1 |
5.8 |
9.5 |
|
100 |
|
33 |
22 |
47 |
47 |
33 |
|
Optidrive VTC Size 3
|
32030 |
32040 |
32055 |
34055 |
34075 |
34110 |
34150 |
| Motor output |
kW |
| (industrial 150%) |
|
|
3.0 |
4.0 |
5.5 |
5.5 |
7.5 |
11.0 |
15.0 |
|
| Model No.
|
ODP - xxxxx-USA |
|
32040 |
32050 |
32075 |
34075 |
34100 |
34150 |
34200 |
| Motor output |
HP |
| (industrial 150%) |
|
|
4.0 |
5 |
7.5 |
7.5 |
10.0 |
15.0 |
20.0 |
|
Supply
voltage/
phases |
V +/- 10% |
|
220-240/ 1
(50% derating) or 3Ø |
380-480/ 3Ø |
Supply fuse or
MCB rating |
A |
|
32 |
32 |
50 |
32 |
32 |
50 |
50 |
Output voltage /
phases |
V |
|
0-240/ 3Ø |
0-480/ 3Ø |
| Output Amps |
A |
| (overloaded 110%) |
|
|
14 |
18 |
25 |
14 |
18 |
25 |
30 |
|
100 |
|
15 |
22 |
|
Optidrive Plus VTC Size 4
| Model No.
|
| ODE/ODEF-xxxxx-IN |
|
42075 |
42110 |
42150 |
42185 |
44220 |
|
7.5 |
11 |
15 |
18.5 |
18.5 |
|
| Model No.
|
| ODE/ODEF-xxxxx-USA |
|
42100 |
42150 |
42200 |
42250 |
44250 |
|
10 |
15 |
20 |
25 |
30 |
|
Supply
voltage/
phases |
V +/- 10% |
|
220-240/ 1 (50% derating) or 3Ø |
Supply fuse or
MCB rating |
A |
|
80 |
80-100 |
100 |
100-125 |
160 |
|
0-240/ 3Ø |
| Output Amps |
A |
| (overloaded 110%) |
|
|
39 |
46 |
61 |
72 |
90 |
|
100 |
|
6 |
|
|
For data on additional drive sizes, please contact us.